Product Main Features:
10000W 48V Pure Sine Wave Inverer + 14850W MPPT Solar Charger + 40A Battery Charger.
Max PV Input 1000Vdc.
Built-in 40A Battery Charger.
Works With 48v Battery System only.
Max Grid-Tie conversion efficiency up to 96%.
High efficiency transformerless design.
Self-consumption and feed-in to the grid.
Programmable supply priority for PV, Battery or Grid.
User-adjustable battery charging current suits different typesof batteries.
Programmable multiple operations modes: Grid tie, Off grid,and grid-tie with backup.
Built-in Timer for various mode of on/off operation.
Multiple communication for USB, RS-232, Modbus and SNMP.
Monitoring software for real time status display and control.
Custom-made firmware by ODM contractParallel operation up to 6 units.
MODEL
|
ANJ-Inifisolar-Plsus-10KW
|
Phase
|
3-phase in / 3-phase out
|
Maximum PV input power
|
14850 W
|
Rated output power
|
10000 W
|
Maximum charging power
|
9600 W
|
GRID-TIE OPERATION
|
PV INPUT(DC)
|
Nominal DC Voltage Maximum
|
720 VDC / 1000 VDC
|
Start-up Voltage lnitial Feeding
|
320 VDC / 350 VDC
|
MPP Voltage Range
|
350 VDC ~ 950 VDC
|
Number of MPP Trackers
|
2 / 2 x 18.6 A
|
GRID OUTPUT(AC)
|
Nominal Output Voltage
|
230 VAC (P-N) / 400 VAC (P-P)
|
Output Voltage Range
|
184-265 VAC* per phase
|
Nominal Output Current
|
14.5 A per phase
|
Power Factor
|
>0.99
|
EFFICIENCY
|
Maximum Conversion
|
96%
|
European Efficiency@Vnominal
|
95%
|
OFF-GRID OPERATION
|
AC INPUT
|
AC Start-up Voltage Auto
|
120 - 140 VAC per phase / 180
|
Acceptable lnput Voltage Range
|
170 - 290 VAC per phase
|
Maximum AC lnput Current
|
40 A
|
PV INPUT(DC)
|
Maximum CD Voltage
|
1000 VDC
|
MPP Voltage Range
|
350 VDC ~ 950 VDC
|
Number of MPP Trackers
|
2 / 2 x 18.6 A
|
BATTERY MODE OUTPUT(AC)
|
Nominal Output Voltage
|
230 VAC (P-N) / 400 VAC (P-P)
|
Output Waveform
|
Pure Sinewave
|
Efffficiency (DC to AC)
|
91%
|
HYBRID OPERATION
|
PV INPUT (DC)
|
Nominal DC Voltage
|
720 VDC / 1000 VDC
|
Start-up Voltage
|
320 VDC / 350 VDC
|
MPP Voltage Range
|
350 VDC ~ 950 VDC
|
Number of MPP Trackers
|
2 / 2 x 18.6 A
|
GRID OUTPUT (AC)
|
Nominal Output Voltage
|
230 VAC (P-N) / 400 VAC (P-P)
|
Output Voltage Range
|
184-264.5 VAC* per phase
|
Nominal Output Current
|
14.5 A per phase
|
AC INPUT
|
AC Start-up Voltage Auto
|
120 - 140 VAC per phase / 180
|
Acceptable lnput Current
|
170 - 290 VAC per phase
|
Maximum AC lnput Current
|
40 A
|
BATTERY MODE OUTPUT (AC)
|
Nominal Output Voltage
|
230 VAC (P-N) / 400 VAC (P-P)
|
Efficiency (DC to AC)
|
91%
|
BATTERY & CHARGER
|
Nominal DC Voltage
|
48 VDC
|
Maximum Charging Current
|
Default 60A, 10A - 200A
|
GENERAL
|
PHYSICAL
|
Dimension,D X W X H (mm)
|
167.5 x 500 x 622
|
Net Weight (kgs)
|
50
|
INTERFACE
|
Communicaltion Port
|
RS-232/USB
|
lntelligent Slot
|
Optional SNMP, Modbus and AS-400 cards available
|
ENVIRONMENT
|
Humidity
|
0 ~ 90% RH (No condensing)
|
Operating Temperature
|
-10 to 55°C
|
Altitude
|
0 ~ 1000 m**
|